Use passive copper inside the rack, active copper for the metres copper cannot cross, and optics for everything between racks — and check the connector on both ends before you order, because on NDR the switch side is OSFP while the adapter side is usually QSFP112, and those two will not mate. That single sentence covers most of the cabling decisions in a 200G HDR or 400G NDR GPU fabric. What follows is the detail behind it: the per-lane signalling each generation uses, the reach each media type is rated for, how port splitting changes your cable count, and the three physical mistakes that cause most of the “link comes up but performs badly” tickets.
The short answer: copper inside the rack, optics between racks
InfiniBand fabrics are built from three media types, and the split between them is decided by distance, not by budget preference. Passive direct attach copper (DAC) has no electronics, draws no port power and adds the least latency, but its reach shrinks as the line rate rises. Active copper adds signal-conditioning electronics to the connector to buy a few more metres. Optical links use either an active optical cable with the transceivers bonded on at both ends, or separate optical transceivers with passive fibre between them.
In practice that means: DAC for server-to-ToR and switch-to-switch inside a rack, active copper or short optics for rack-to-adjacent-rack, and optics for anything crossing a row, a hall or a building. A cable plan that mixes these up does not fail at design time — it fails six weeks later when a link starts logging errors under load.
What changes from EDR to HDR to NDR
The generational jump is not a new protocol. It is more bits per lane per clock, using a denser modulation, packed into the same four-lane electrical structure.
EDR carries 100 Gb/s as four lanes of 25G NRZ. HDR carries 200 Gb/s as four lanes of 50G PAM4. NDR carries 400 Gb/s as four lanes of 100G PAM4, and the lane electrical interface behind it is the 112G class — which is where the QSFP112 name comes from. It is worth saying plainly: 112 in QSFP112 refers to the per-lane signalling rate, not to a physical dimension.
Because the lane count stays at four, the reach penalty of going faster shows up almost entirely in copper. Doubling the signalling rate roughly halves the usable copper distance, which is exactly what the numbers in the next sections show. The same progression also explains why an older 100G EDR fabric built on 36-port EDR switching still works perfectly well for storage and management planes while the compute plane moves to 400G.
Connector discipline: QSFP28, QSFP56, QSFP112 and OSFP
Four connector families appear across these three generations, and only two of them are physically identical in outline while being electrically different.
QSFP28 is the EDR cage: four 25G NRZ lanes. QSFP56 keeps the QSFP outline but runs four 50G PAM4 lanes for HDR. QSFP112 keeps the QSFP outline again and runs four 100G PAM4 lanes for NDR at the adapter end. That means a QSFP56 HDR cable and a QSFP112 NDR cable can look the same in a photo and fit the same cage, while supporting different lane rates. Ordering by appearance is the most common sourcing error in this generation.
On the switch side, NDR moved to OSFP. A Quantum-2 NDR switch fits 64 ports into 1U by using 32 OSFP cages with two NDR ports per cage, which is why the port count is double the connector count. The OSFP cages on those switches accept finned OSFP connectors only, because the fins are part of how the port array is cooled; flat OSFP is the single-port variant used at adapters, with the second port position physically blocked. A switch-to-adapter NDR link therefore has a finned OSFP on one end and a flat OSFP or QSFP112 on the other — and the part number must say so. Our 64-port NDR Quantum-2 switch is a good reference point for what that cage layout looks like in a 1U chassis.
Passive DAC reach: the numbers you can plan against
These are the copper ceilings that matter when you draw the rack elevation.
At EDR 100G, passive DAC is available in lengths up to 5 m, which is enough to reach the top of a 42U rack from a mid-rack ToR. At HDR 200G, passive copper tops out at 2 m, with standard lengths at 0.5, 1, 1.5 and 2 m. At NDR 400G and above on OSFP, the passive copper ceiling is 3 m.
Two details are easy to miss. First, the 2 m HDR figure and the 3 m NDR figure are not a contradiction — they come from different cable families with different gauge and connector designs, so always confirm the figure for the specific part rather than the speed. Second, all of these are straight-cable figures; the splitter variants are shorter, typically 1 to 2 m passive, because the same signal budget has to survive an extra connector.
Active copper and LACC: the middle distance
Between “fits in the rack” and “needs fibre” there is a band that copper can still cover if you add electronics at the connector.
For HDR, active copper extends the reach to 4 m, at a cost of about 3.5 W drawn from each InfiniBand port — a number that matters when you are counting port power across 64 ports. For the 400G and 800G OSFP generation, linear active copper reaches 5 m. The trade is straightforward: you pay more per cable and add a small amount of power and latency, and in exchange you avoid a transceiver pair and keep the link inside a single rack-to-rack hop.
Active copper is also thinner than passive copper at the same rate, which is a real benefit in a 64-port switch where cable diameter, not cable count, is what blocks airflow.
Optical reach and the MPO/APC change
Once a link leaves the rack row, optics take over, and here the HDR and NDR generations diverge in a way that has bitten a lot of teams during migration.
For HDR 200G, the short-reach module is an MPO-12 receptacle for passive 8-fibre multimode cable with a 100 m reach and up to 5 W draw from the port; point-to-point links use a Type B (reversed) MPO jumper, with the middle four of the twelve fibre positions unpopulated. The long-reach HDR module is duplex LC single-mode with a 2 km reach, combining the four lanes onto one fibre per direction using coarse wavelength division multiplexing.
NDR fibre changed the polish. NDR optical links use MPO/APC — angled physical contact — for better signal integrity at 100G per lane, and MPO/APC is not interoperable with the earlier MPO cables in an HDR plant. If you are upgrading a fabric in place, the fibre trunks between racks are the item most likely to need replacing, and they are also the item with the longest procurement lead time. Reach classes for 400G optics are typically 500 m for DR and 2 km for FR.
One planning caution on AOC: NVIDIA’s cabling design guide lists 150 m as the HDR active optical ceiling, while 200G AOC product literature has quoted 100 m. Plan to the shorter number unless the exact part is confirmed, and never design to the optimistic end of a range.
Splitters: 200G to 2x100G, 400G to 2x200G
Port splitting is where cable counts and cost models change most, and it is the feature most often misunderstood as “free bandwidth”.
An HDR 200G port uses four 50G lanes. A splitter presents two HDR100 ports of two lanes each, so one 200G switch port serves two 100G hosts that need half the width. Passive HDR splitters are available at 1, 1.5 and 2 m, with active versions at 3 and 4 m. The same logic scales to NDR: a 400G port can be split into two 200G NDR200 ports, which is how a 64-port NDR chassis presents up to 128 ports of 200G.
Two rules keep this clean. Aggregate bandwidth per cage does not increase — you are dividing a fixed number of lanes, not adding capacity. And splitting is a property of the port and the cable, not something you can apply selectively per packet, so an oversubscription ratio has to be designed per host group. The adapter side matters too: our dual-port HDR100 adapter is the kind of host end that pairs naturally with a split 200G port, while a full-width dual-port 200G HDR adapter should get its own non-split port.
Comparison table: one cable type per link rate
| Link rate | Signalling | Connector | Passive copper | Active copper | Optical |
|---|---|---|---|---|---|
| EDR 100G | 4 x 25G NRZ | QSFP28 | up to 5 m | not required | MMF short reach, SMF long reach |
| HDR 200G | 4 x 50G PAM4 | QSFP56 | up to 2 m | up to 4 m, about 3.5 W per port | AOC 100 to 150 m; 100 m MMF; 2 km SMF |
| HDR100 100G (split) | 2 x 50G PAM4 | QSFP56, 2 lanes | 1 to 2 m splitter | 3 to 4 m splitter | same optics family as HDR |
| NDR 400G | 4 x 100G PAM4 | OSFP at switch, QSFP112 at adapter | up to 3 m | LACC up to 5 m | DR 500 m, FR 2 km, MPO/APC |
| NDR200 200G (split) | 2 x 100G PAM4 | OSFP to 2 x QSFP112 | up to 3 m splitter | LACC splitter | DR 500 m, FR 2 km, MPO/APC |
Counting cables for a rail-optimised fabric
In a rail-optimised design, each GPU in a node has its own rail, and each rail connects to a separate leaf switch. The cable count is therefore driven by GPUs times rails, not by nodes.
An eight-GPU node with eight 400G adapters produces eight fabric links per node, all of which land on different leaves. For a 32-node cluster that is 256 switch-to-adapter links before you count the spine layer. At 3 m of passive copper per link you can usually keep the compute plane inside the rack and take the spine layer optical; at 400G the alternative is a large and expensive transceiver population on both ends, which is exactly the trade that port splitting is meant to soften.
Uniform cable lengths are worth insisting on. Fabric managers expect symmetric electrical characteristics across a rail, and a mixed bag of 1 m and 3 m cables in the same rail group makes link-width and error-rate comparison between ports meaningless. Our QM9790 400G NDR chassis and the QM9700 above take the same OSFP cabling approach, so a spare-cable pool built for one works for both.
Bend radius, diameter and airflow
Cable diameter is a thermal decision in a dense switch, and bend radius is an error-rate decision. Both get ignored because neither appears in a bandwidth table.
For a typical four-channel QSFP AOC, the cable diameter is about 3 mm, with guidance of 15 times diameter as a dynamic minimum bend radius and 10 times diameter as a static one — roughly 45 mm and 30 mm — and about 56 mm for the cable-plus-connector assembly. Bend a fibre tighter than that and light reflects abnormally at the bend, which shows up as intermittent errors rather than a dead link. Passive copper is far less forgiving of tight radius than fibre and much heavier, so route it first and route it low.
Bringing links up: diagnosis and a bill of materials
A link that trains at reduced width is the most common symptom of a marginal cable, and it is diagnosable without swapping hardware at random.
Check the negotiated width and speed of the port first: a four-lane link that comes up as two lanes or one lane is almost always a damaged lane, a contaminated connector, or a cable run beyond its rated reach. Then check the error counters on both ends; a run of symbol errors that grows under load points to reach or bend radius rather than to a dead transceiver. Finally confirm that both ends agree on the expected speed — a port configured or licensed for a lower rate will negotiate down quietly and look healthy while delivering half the bandwidth.
A workable bill of materials for a new NDR rack therefore has five lines: passive DAC in 1 m and 3 m for in-rack links, a small quantity of LACC in 5 m for the rack-adjacent hops, optical transceivers in DR and FR classes with MPO/APC trunks, splitter cables matched to the hosts that need half width, and a labelled spare of each. Label the finned and flat OSFP parts differently on the shelf — that is the mistake that costs an afternoon.
Frequently Asked Questions
Can I plug a QSFP56 HDR cable into a QSFP112 NDR port?
Physically it may fit, because QSFP56 and QSFP112 share the QSFP outline and differ mainly in rated lane signalling. Electrically it will not deliver 400G: the cable and the module are rated for 50G PAM4 lanes, so the link either negotiates to the lower rate or fails to train. Match the cable’s lane rating to the port’s advertised speed, and treat the connector outline as necessary but not sufficient.
How far can 400G NDR passive copper actually reach?
Three metres for the OSFP passive DAC family, with 5 m available from linear active copper. Beyond that, optics. Because the reach figure is a property of the specific cable family rather than of the speed alone, confirm the rated length for the exact part number before you commit a rack design to it.
Does splitting a 400G port into two 200G ports lose bandwidth?
No bandwidth is lost at the cage, because the cage still carries 400G in total, but each host now sees 200G instead of 400G. The effect is a change in per-host oversubscription, not a change in switch capacity, and it should be decided per host group rather than applied across a whole fabric.
Are HDR and NDR fibre cables interchangeable?
No. NDR optical links use MPO/APC angled connectors for signal integrity at 100G per lane, and these are not interoperable with the earlier MPO connectors used at HDR. The transceiver form factors differ as well, so an in-place upgrade usually means new fibre trunks between racks, which is the longest-lead item in the plan.
Can a 400G NDR switch port run at 200G for older hosts?
Yes, within the generation’s stated backwards-compatibility envelope: an NDR port can operate at HDR 200G, and a split port can present 200G or 100G-class links to slower hosts. What does not work is asking a 100G EDR switch to carry 400G — the port rate ceiling is set by the switch ASIC and its optics, not by the cable.
If you are laying out an HDR or NDR fabric and need the cable, switch and adapter ends to agree on the first order, send us the rack elevation and the host list on WhatsApp at +86 13068616914. Switches, adapters and the port-split options discussed above are listed with part numbers and confirmed availability on zhongxindata.hk, so you can check model-level detail before committing a bill of materials.
Request a quote for this configuration